[email protected] / www.tuncmatik.com NEWTECH PRO 1-2-3 KVA ONLINE UNINTERRUPTIBLE POWER SUPPLY USER MANUAL
9 3-3. Audible Alarm Battery Mode Sounding every 4 seconds Low Battery Sounding every second Overload Sounding twice every second Fault Continuousl
10 01: Output voltage setting Interface Setting Parameter 3: Output voltage For 208/220/230/240 VAC models, you may choose the following output v
11 LLS: Low loss voltage in ECO mode in parameter 2. For 208/220/230/240 VAC models, the setting range in parameter 3 is from -7V to -24V of the nomi
12 3-6. Operating Mode Description Operating mode Description LCD display Online mode When the input voltage is within acceptable range, UPS will p
13 3-8. Warning indicator Warning Icon (flashing) Alarm Low Battery Sounding every second Overload Sounding twice every second Battery is not c
14 4. Troubleshooting If the UPS system does not operate correctly, please solve the problem by using the table below. Symptom Possible cause Reme
15 display and alarm is continuously sounding. short circuit occurs on the UPS output. short circuit status. Fault code is shown as 1, 2, 3, 4, 11, 1
1 Table of Contents 1. Important Safety Warning……………………………………………… 2 1-1. Transportation 2 1-2. Preparation 2 1-3. Installation 2 1-4. Operation 2 1-5
2 1. Important Safety Warning Please comply with all warnings and operating instructions in this manual strictly. Save this manual properly and read
3 1-5. Maintenance, service and faults The UPS system operates with hazardous voltages. Repairs may be carried out only by qualified maintenance p
4 2. Installation and setup NOTE: Before installation, please inspect the unit. Be sure that nothing inside the package is damaged. Please keep the
5 2-2. Setup the UPS Step 1: UPS input connection Plug the UPS into a two-pole, three-wire, grounded receptacle only. Avoid using extension cords.
6 Step 4: Network connection Network/Fax/Phone surge port Connect a single modem/phone/fax line into surge-protected “IN” outlet on the back panel o
7 3. Operations 3-1. Button operation Button Function ON/Mute Button Turn on the UPS: Press and hold ON/Mute button for at least 2 seconds to
8 Display Function Backup time information Indicates the backup time in pie chart. Indicates the backup time in numbers. H: hours, M: minute, S